亚洲在线视频 I 色哟哟av I 国产精品呻吟 I 男人的天堂影院 I 男女一级片 I 黄色小说免费在线观看 I 99成人免费视频 I 欧美性猛交xxxx黑人交 I 四虎永久在线精品免费一区二区 I 空姐吹箫视频大全 I 成人黄色在线播放 I 奇米影视第四色7777 I 青青草免费看 I 色网站在线免费观看 I 岛国伊人 I 亚洲精品合集 I 久久77777 I 久久色中文字幕 I 91亚洲视频在线 I 亚洲国产精品成人综合在线 I 国语自产少妇精品视频 I 激情小说第一页 I 狠狠综合色 I 午夜一区二区国产好的精华液 I 成人国产二区 I 东北妇女xx做爰视频 I 国产日产欧产美韩系列麻豆 I 成人美女黄网站色大免费的

Welcome to JIANGSU YUANTONG ELECTRIC CO.,LTD.

News

Follow our fresh news anytime, anywhere
Causes and Treatment of Transformer Backup Protection Action
發布時間:2020-05-11 16:02:26 瀏覽量:811

Causes and Treatment of Transformer Backup Protection Action

--------------------------------------------------------------------------------

The reason for the backup protection action of the transformer is:

(1) Short circuit on the high-voltage side of the transformer.

(2) Transformer low voltage bus short circuit.

(3) Due to a fault occurring within the range of differential protection, the differential protection failed.

(4) Backup protection malfunction.

(5) There is a fault in the low-voltage line, and the outgoing line protection refuses to operate, causing the transformer to overload and trip.

The handling principle is:

(1) If the overcurrent protection is activated and phenomena such as voltage drop, impact, arc light, sound, etc. are found, the external part of the transformer should be inspected; If the fault can be eliminated in a timely manner, it can be tested once, otherwise safety measures should be taken to prepare for repair; If no issues are found, a test drive can also be performed; For transformers without differential protection, in addition to external inspection, insulation measurement inspection should also be carried out.

(2) If the low-voltage outgoing line malfunctions and the line protection refuses to operate, the faulty line switch can be manually turned off and the transformer can be powered on.

(3) If a fault occurs within the differential protection range and the differential protection fails, it should be handled according to the differential protection action.

(4) If it is a secondary circuit fault, it is a misoperation or accidental touch, and the duty personnel can immediately test the power supply.